Communication
- Ethernet modules are covered by IEEE802.3 standard and supports ARP, ICMP, IP, TCP, UDP protocols.
- There is No limitation number of Ethernet module installation in one base but the maximum number of expansion modules in one base is 11 modules.
- It operates with CIMON-SCADA to support Dynamic IP(DHCP).
- It supports MODBUS/TCP Master function.
- It supports High-speed link to communicate along Cimon PLCs and 64 simultaneous communications.
- In case of High Speed PLC link, maximum 4 Ethernet modules can be installed.
Ethernet module
Module specification
Item | CM3-SP01EET | |
---|---|---|
Media interface | 10BASE-T, 100BASE-TX | |
Transmission speed | 10/100Mbps | |
Max. length of segment | 100m | |
Service capacity | UDP, TCP : 12 Service | |
Service | Loader | Yes (UDP) |
HMI Protocol | Yes (TCP, UDP) | |
MODBUS/TCP SI. | Yes | |
MODBUS/TCP Ms. | Yes | |
PLC Link(Exclusive) | No | |
PLC Link(Common) | No | |
High-speed PLC Link | Yes | |
DHCP | Yes |
Cable Specification-(UTP)
Item | Unit | Value | |
---|---|---|---|
Conductor resistance (Maximum) | Ω / km | 93.5 | |
Insulation resistance (Minimum) | MΩ / km | 2500 | |
Withstand voltage | V / 분 | AC 500 | |
Impedance | Ω (1 ~ 100MHz) | 100±15 | |
Attenuation | Ω (1 ~ 100MHz) | 10 | 6.5 |
16 | 8.2 | ||
20 | 9.3 | ||
Attenuation | Ω (1 ~ 100MHz) | 10 | 47 |
16 | 44 | ||
20 | 42 |
※The cable type should be selected according to system configuration and circumstance.
Therefore, please install it after consulting with the experts.
Serial module
- Independent operation by channel with 3rd party protocol RS-232C and RS422/485 channels.
- Read and write data through HMI protocol.
- Supports HMI protocol for Multi drop (Max. 32units communication available)(RS422/485)
- CDMA modem is built in some of serial modules to control far away PLC.(RS232C)
- Supports wide range of communication speed (300bps~38400bps)
- RS232C/RS422/485 Comm. port can be used as independent channel or linked channel.
- Supports 1:1 / 1:N / N:M in case of RS422/485.
- Supports Full-Duplex(RS422) and Half-Duplex(RS485).
- Supports MODBUS/RTU Master function.
- RS422/485 channels are photo coupler insulation to prevent noise.
Module specification
Model | SP02ERS | SP02ERR | SP02ERC | SP02ERSC | SP02ERRC | |
---|---|---|---|---|---|---|
Interface | RS232C:1CH RS422/485:1CH |
RS232C: 2CH | RS232C: 1CH | RS232C:1CH RS422/485:1CH |
RS232C: 2CH | |
Communication method | Null modem | O | O | O | O | O |
Cable modem | O | O | O | O | O | |
CDMA modem | O | O | O | O | O | |
Operation mode | Protocol Special program |
User defined protocol program | ||||
HMI protocol | CIMON-PLC HMI Protocol | |||||
MODBUS Protocol |
Modbus RTU Protocol | |||||
Graphic Loader Loader Protocol |
Control PLC through CICON connection function | |||||
ModBus Master Master protocl |
Communicate to Modbus RTU slave | |||||
Data type | Data bit | 8 bit | ||||
Stop bit | 1 or 2 bit | |||||
Parity | Even / Odd / None | |||||
Synchronous | Asynchronous | |||||
Transmission speed(bps) | 300 / 600 / 1200 / 2400 / 4800 / 9600 / 19200 / 38400 | |||||
Insulation method | RS232C: N/A RS422/485: Photo-coupler insulation |